| Supply voltage |
| Load voltage L+ |
| ● Rated value (DC) |
24 V |
| ● Reverse polarity protection |
Yes |
| Input current |
| from load voltage L+ (without load), max. |
80 mA |
| from backplane bus 3.3 V DC, max. |
10 mA |
| Power losses |
| Power loss, typ. |
1.9 W |
| Address area |
| Address space per module |
| ● Address space per module, max. |
4 byte |
| Analog inputs |
| Number of analog inputs |
2 |
| permissible input voltage for voltage input (destruction limit), max. |
35 V |
| Cycle time (all channels) max. |
250 µs |
| Input ranges |
| ● Voltage |
Yes |
| ● Current |
No |
| ● Thermocouple |
No |
| ● Resistance thermometer |
No |
| ● Resistance |
No |
| Input ranges (rated values), voltages |
| ● 1 to 5 V |
Yes |
| ● Input resistance (1 to 5 V) |
120 kΩ |
| ● -10 V to +10 V |
Yes |
| ● Input resistance (-10 V to +10 V) |
120 kΩ |
| ● -2.5 V to +2.5 V |
Yes |
| ● Input resistance (-2.5 V to +2.5 V) |
120 kΩ |
| ● -5 V to +5 V |
Yes |
| ● Input resistance (-5 V to +5 V) |
120 kΩ |
| Cable length |
| ● Cable length, shielded, max. |
200 m |
| Analog value creation |
| Integration and conversion time/resolution per channel |
| ● Resolution with overrange (bit including sign), max. |
16 bit |
| Smoothing of measured values |
| ● Parameterizable |
Yes |
| ● Step: None |
Yes |
| ● Step: low |
Yes |
| ● Step: Medium |
Yes |
| ● Step: High |
Yes |
| Encoder |
| Connection of signal encoders |
| ● for voltage measurement |
Yes |
| Errors/accuracies |
| Linearity error (relative to input range), (+/-) |
0.03 % |
| Temperature error (relative to input range), (+/-) |
0.01 %/K |
| Crosstalk between the inputs, min. |
-50 dB |
| Repeat accuracy in steady state at 25 °C (relative to input area), (+/-) |
0.1 % |
| Operational limit in overall temperature range |
| ● Voltage, relative to input area, (+/-) |
0.3 % |
| Basic error limit (operational limit at 25 °C) |
| ● Voltage, relative to input area, (+/-) |
0.2 % |
| Isochronous mode |
| Isochronous operation (application synchronized up to terminal) |
Yes |
| Interrupts/diagnostics/status information |
| Alarms |
| ● Hardware interrupt |
Yes |
| Diagnostic messages |
| ● Diagnostic functions |
Yes |
| ● Diagnostic information readable |
Yes |
| ● Wire break |
Yes |
| ● Group error |
Yes |
| ● Overflow/underflow |
Yes |
| Diagnostics indication LED |
| ● Group error SF (red) |
Yes |
| Galvanic isolation |
| Galvanic isolation analog inputs |
| ● between the channels |
No |
| ● between the channels and the backplane bus |
Yes |
| ● between the channels and the load voltage L+ |
Yes |
| Dimensions |
| Width |
15 mm |
| Height |
81 mm |
| Depth |
52 mm |
| Weights |
| Weight, approx. |
45 g |
| last modified: |
16.09.2014 |